Internal Product Review

The FC-301P3K7T2134L2181 is a Danfoss VLT FC 301 automation drive rated at 3.7 kW for 200-240 VAC input. High efficiency at rated current of 0.96 and a displacement power factor above 0.98 support clean, dependable drive performance in demanding industrial service.

Sell Part
Have a part to sell?
Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

The FC-301P3K7T2134L2181 is an AC variable frequency drive manufactured by Danfoss for the VLT FC 301 Automation Drives series. Within automated machinery, it sits between the three-phase mains and an induction motor, modulating voltage and frequency so the controller can match shaft speed to process demand. This electronic regulation removes the need for mechanical throttling, improves energy use, and provides precise torque control for conveyors, pumps, and general material-handling equipment.

Incoming power compatibility is 200–240 VAC, and the drive is wired for three-phase feeders to keep conductor currents balanced. At 230 V, the continuous apparent power reaches 6.65 kVA, while efficiency at rated current is 0.96, indicating low internal loss. The resulting power loss is 185 W, a value that can be used to determine enclosure ventilation requirements. The microprocessor can increase motor speed because the adjustable output extends to 590 Hz, well above the base line frequency and suitable for oversynchronous operation when high spindle surface velocity is required.

The inverter delivers a mechanical output of 3.7 kW, and magnetic excitation remains linear up to a flux frequency of 300 Hz, ensuring consistent torque during fast cycles. Shielded cable runs are limited to 50 m, while unshielded leads can extend to 75 m to maintain rise-time and EMC compliance. Phase imbalance must remain below 3.0%, and the digital control inputs tolerate up to 28 V DC, preventing damage from typical sensor voltages. The drive permits two power-ups per minute without triggering inrush protection. Its displacement power factor is greater than 0.98, while its true power factor is at least 0.9, allowing the unit to draw current efficiently. Output voltage can be commanded up to the full supply level for effective motor control across the available operating range.

Cont. Apparent Power
6.65 kVA @230 V
Displacement Power Factor
>0.98
Efficiency At Rated Current
0.96
Horse Power
5.0 HP
Mains Voltage
200 - 240 VAC
Max Digital Input Voltage
28 V DC
Max Flux Frequency
300 Hz
Max Output Frequency
590 Hz
Max Output Voltage
100% of supply voltage
Max Phase Imbalance
3.0%
Max Power-ups
2/min
Max Shielded Motor Cable
50 m
Max Unshielded Motor Cable
75 m
Power Loss At Rated Load
185 W
Power Phase
Three Phase Power
Power Rating
3.7 KW
Product Group
VLT AutomationDrive FC
Series Identifier
301
True Power Factor
≥0.9

Frequently Asked Questions about FC-301P3K7T2134L2181:

Q: What input voltage range is supported by the FC-301P3K7T2134L2181 drive?

A: The FC-301P3K7T2134L2181 drive supports a mains voltage range of 200 to 240 VAC for flexible installation.

Q: What is the power rating of the FC-301P3K7T2134L2181 drive?

A: This model delivers a power rating of 3.7 kW, making it suitable for medium-duty automation tasks.

Q: What is the highest output frequency the FC-301P3K7T2134L2181 can deliver?

A: The maximum output frequency for this unit is 590 Hz, allowing for high-speed motor control applications.

Q: What is the power loss of the FC-301P3K7T2134L2181 drive at full load?

A: At its rated load, the FC-301P3K7T2134L2181 experiences a power loss of 185 W during operation.

Q: What is the maximum length for shielded motor cables with the FC-301P3K7T2134L2181?

A: The drive has a maximum shielded motor cable length of 50 meters, enabling installation flexibility.