4.94 based on 219 reviews

🙶 Wake was very helpful in getting us a servo motor and drive for our tube mill line. This was the first tim... 🙷

FC-301P18KT4131F5388 Danfoss

Ask for Availability
No Hidden Fees Rush or Credit Card
No Tariffs On US Orders

Internal Product Review

The FC-301P18KT4131F5388 is a Danfoss VLT FC 301 automation drive rated at 18.5 kW and 25 HP. High operating efficiency of 0.98 and 37.5 A continuous output current support stable motor control in demanding three-phase applications. Mains compatibility across 380 to 480 VAC makes this drive a strong choice for flexible industrial integration.

Sell Part
Have a part to sell?
Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

The FC-301P18KT4131F5388 is a variable frequency drive manufactured by Danfoss for the VLT FC 301 Automation Drives series. It converts fixed-frequency three-phase input into a regulated, pulse-width-modulated output, letting control systems adjust motor speed without mechanical throttling. This product sits in the mid-power class of the platform and is used on conveyors, pumps, and ventilation equipment where accurate speed regulation, torque ramping, and integrated protection functions enhance plant efficiency.

It connects to industrial feeders rated at 380–480 VAC and provides a continuous motor output of 18.5 kW. Under those conditions, the inverter delivers a steady motor phase current of 37.5 A. For starting or acceleration events, it can supply up to 60 A for one minute before reverting to the nominal load. Conversion efficiency reaches 0.98, so only a small fraction of the incoming power is dissipated as heat. The control algorithm can extend the motor speed range by raising the fundamental frequency to a maximum output of 590 Hz, supporting high-speed spindles or compact blower drives. The apparent input power at 400 V is 26 kVA, and the DC-link brake chopper activates at 778 V DC to absorb regenerated energy.

At rated conditions, the module produces only 444 W of heat, easing enclosure ventilation calculations and allowing installation in compact cabinets. The monitoring circuit issues a high-voltage warning at 810 V DC, allowing regenerative conditions to be identified before the 820 V DC alarm forces a controlled shutdown. Motor leads can run up to 50 m when shielded, enabling remote drive placement while keeping conducted emissions within acceptable limits. The shielded cable should be routed according to the applicable installation practices to preserve electromagnetic compatibility. Adequate cabinet airflow helps remove conversion losses during continuous operation. The brake circuit must also be selected to accommodate energy returned by the connected motor during deceleration.

Brake Active Dc Link
778 V DC
Cont Apparent Power (@400 V)
26 kVA
Cont Input Current (ho, 380-440 V)
34 A
Cont Output Current (ho, 380-440 V)
37.5 A
Efficiency At Rated Current
0.98
High-voltage Warning
810 V DC
Horse Power
25 HP
Mains Voltage
380 - 480 VAC
Max Flux Frequency
300 Hz
Max Output Frequency
590 Hz
Max Power-ups
1/min
Max Shielded Motor Cable
50 m
Max Unshielded Motor Cable
75 m
Overload Output Current (ho, 380-440 V)
60 A
Overvoltage Alarm
820 V DC
Power Loss At Rated Load
444 W
Power Phase
Three Phase Power
Power Rating
18.5 KW
Product Group
VLT AutomationDrive FC
Series Identifier
301

Frequently Asked Questions about FC-301P18KT4131F5388:

Q: What is the power rating and horsepower of the FC-301P18KT4131F5388 drive?

A: The FC-301P18KT4131F5388 has a power rating of 18.5 kW, which translates to 25 horsepower.

Q: What is the mains voltage range for the Danfoss FC-301P18KT4131F5388?

A: This drive supports a mains voltage range from 380 to 480 VAC for flexible installation in various industrial systems.

Q: What is the maximum output frequency of the FC-301P18KT4131F5388?

A: The maximum output frequency for the FC-301P18KT4131F5388 is 590 Hz, allowing for high-speed motor applications.

Q: What efficiency can be expected from the FC-301P18KT4131F5388 at rated current?

A: At rated current, this drive achieves an efficiency of 0.98, minimizing energy losses during operation.

Q: What is the continuous output current for the FC-301P18KT4131F5388 at 380-440 V?

A: The FC-301P18KT4131F5388 can handle a continuous output current of 37.5 A when supplied with 380-440 V.

Motion Industries logo
3M logo
IBM logo
Gexpro Logo
Caterpillar logo
NASA logo
Ford logo
Vallen logo