FC-301P15KT4134L2690 Danfoss
Wake Industrial LLC is not an authorized distributor of this product.
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
The Danfoss FC-301P15KT4134L2690 is part of the VLT FC 301 Automation Drives series and is rated for 20 HP or 15 kW with a mains voltage range of 380 to 480 VAC. This drive offers three phase power, a maximum output frequency of 590 Hz, and an efficiency at rated output of 0.98. It features two 10-bit analog inputs, one 12-bit analog output, and two digital outputs with a maximum frequency of 32 kHz.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The FC-301P15KT4134L2690 is an AC variable frequency drive manufactured by Danfoss for the VLT FC 301 Automation Drives series. By converting fixed-frequency three-phase input into controlled output power, it allows motor speed and torque to be matched to real-time process demands in pumps, fans, and material-handling systems. Its compact enclosure and midrange capacity support installation in control cabinets where thermal dissipation and available space are limited.
The drive accepts an input range of 380 - 480 VAC and can deliver up to 15 kW of electrical power, which corresponds to approximately 20 HP at the motor shaft. Its efficiency is 0.98 at rated load, reducing the amount of waste heat that must be removed through cabinet ventilation. Vector control permits a fundamental output frequency as high as 590 Hz, providing speed overhead for high-speed spindles. A separate 300 Hz flux limit protects standard motor insulation during operation. The inverter operates exclusively on three-phase power. It also limits mechanical and electrical stress by permitting no more than one power-up per minute, which helps protect the DC link from repetitive inrush current.
Two analog inputs are sampled at 10-bit resolution, allowing the drive to process analog references with consistent precision. One analog output is generated at 12-bit resolution for transmitting a proportional process or operating signal. Two digital outputs can switch at 32 kHz for status signaling or simulated encoder pulses. Shielded motor cables may run up to 50 m, supporting installations where electromagnetic interference must be controlled. Unshielded motor cables can extend to 75 m where electromagnetic compatibility requirements permit their use. These cable options allow the drive to connect with motors positioned at different distances from the control cabinet without changing the primary control interface.