VLT 3016
Wake Industrial LLC is not an authorized distributor of this product.
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
-
Available
The VLT 3016 is a variable speed drive providing a constant torque output power of 11 kW at both 230V and 415V mains voltage. Manufactured by Danfoss, it is part of the VLT 3000 Variable Speed Drives series and supports mains voltage ranges of 3x200 to 240V. It handles a maximum branch fuse of 80A at 230V.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The Danfoss VLT 3016 frequency regulator is designed for controlling asynchronous motors in industrial automation applications. Its output power rating is 11 kW when used for constant torque operations. The power factor remains stable at 0.9 under full-rated load. The full load efficiency is measured at around 96%.
The VLT 3016 frequency regulator functions with an input voltage range of 380 to 415 volts AC in a three-phase configuration. The input frequency is supported between 50 and 60 Hertz. The output voltage is adjustable up to the supply line level. The output frequency is programmable from 0 to 500 Hertz, depending on application needs. The unit provides a continuous output current of 24 A. For temporary overload conditions, it allows up to 38.4 A for 60 seconds. In CT mode, the input current draws 21.8 A. For electrical safety, a 63 A input fuse is recommended. This VLT 3016 frequency regulator supports motor cable lengths up to 1000 feet when unshielded. It accepts analog control signals such as 0–10V and 4–20mA. The Digital pulse input frequencies of 100Hz and 1kHz are also supported. The RS-485 communication is provided via terminals 68 and 69 for integration into automation networks. The built-in PID controller enables process feedback and regulation without external devices.
The ramping times of the VLT 3016 frequency regulator can be set from 0.1 seconds up to 3600 seconds. The supported rated motor frequencies include 50Hz, 60Hz, 87Hz, and 100Hz. The device functions reliably in ambient temperatures ranging from -10°C to +40°C. Vibration resistance is rated at 0.7 g RMS for stable operation in dynamic conditions. It can be stored in environments between -25°C and +65°C. The unit complies with EMC standards as defined by EN, IEC, and VDE.
Frequently Asked Questions about VLT 3016:
Q: What ramp settings affect the VLT 3016 frequency regulator?
A: The VLT 3016 frequency regulator allows long and short ramp durations for load handling. This customization ensures optimal deceleration without triggering faults.
Q: How does the VLT 3016 frequency regulator manage high frequencies?
A: The VLT 3016 frequency regulator outputs up to 500 Hz for specialized motors. This supports spindle drives and other high-speed asynchronous applications.
Q: What cabling limits apply to the VLT 3016 frequency regulator?
A: The VLT 3016 frequency regulator supports motor cables up to 1000 feet unshielded. This enables remote motor placement without complex shielding requirements.
Q: How does Danfoss ensure durability in the VLT 3016 regulator?
A: Danfoss designed the VLT 3016 frequency regulator to resist 0.7 g vibration. This ruggedization supports stable performance in mobile and high-impact installations.
Q: What ambient range supports the VLT 3016 frequency regulator?
A: The VLT 3016 frequency regulator operates reliably from –10 °C to +40 °C. This thermal capacity enables installation in unconditioned or semi-exposed locations.