VACON0100-3L-0016-4-HVAC+SBF2+IP54+DLDE
Wake Industrial LLC is not an authorized distributor of this product.
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
The Danfoss VACON0100-3L-0016-4-HVAC+SBF2+IP54+DLDE belongs to the VACON 100 Industrial Drives series and supports 3-phase input voltage of 380-500V AC. It has a nominal current of 16A and an output frequency range of 0-320Hz. The drive delivers 7.5 kW motor power under both high and low load conditions.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
VACON0100-3L-0016-4-HVAC+SBF2+IP54+DLDE is a VACON HVAC drive. Its rated output current is 16 Amps. The drive features an MR5 enclosure size and connects to an AC input of 380 to 480 Volts, drawing 15.4 Amps of input current. At low loadability, the 10% overload current is 17.6 Amps. Under these conditions, it delivers an output power of 7.5 kilowatts (10 Horsepower) to the motor shaft at 40 °C. Weight of the VACON0100-3L-0016-4-HVAC+SBF2+IP54+DLDE drive unit is approximately 10 kilograms. The drive is suited to wall mounting. It comes is an IP54 rated housing that provides superior ingress protection. The AC drive unit has a height of 419 millimeters and a width of 144 millimeters. Depth of the drive unit is approximately 213 millimeters. For optimal performance the input frequency should range from 50 to 60 Hertz.
Starting delay for this drive unit is approximately 6 seconds. The drive can withstand a network imbalance of up to ±3% of the nominal input. It supports TT, IT, and TN mains types, with a maximum allowable peak short-circuit current of 100 kiloamps. Output voltage of the VACON0100-3L-0016-4-HVAC+SBF2+IP54+DLDE drive can range from 0 to the maximum input. The output frequency range spans from 0 to 320 Hertz, with a frequency resolution of 0.01 Hertz. The switching frequency can be set between 1.5 and 10 kilohertz, with a default setting of 6 kilohertz. In the event of overload, the drive is designed to automatically derate the switching frequency. The filed weakening point range is 8 to 320 Hertz. Acceleration and deceleration times are adjustable between 0.1 and 3000 seconds. The recommended ambient operating temperature for the drive is -10 to 40 °C. Documentation for the drive is available in German.
Frequently Asked Questions about VACON0100-3L-0016-4-HVAC+SBF2+IP54+DLDE:
Q: What is the starting delay?
A: The starting delay is 6 seconds.
Q: What is the output t voltage range?
A: The output voltage range is from 0 to the input voltage.
Q: What is the range of switching frequencies?
A: The range of switching frequencies is 1.5 to 10 kilohertz.
Q: What is the mounting orientation?
A: Mounting orientation of the drive is vertical.
Q: What is the operating temperature range?
A: The operating temperature range is -10°C to +40°C.