NFD02.2-480-030 Bosch Rexroth Indramat
MPN: R911279997
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
The Bosch Rexroth Indramat NFD02.2-480-030 is part of the NFD Mains Filters series and is designed for AC mains voltages up to 480 V with a rated mains current of 30 Amps. This three-phase filter offers an overload capacity of 1.5 times nominal current for 1 minute per hour and has a protection rating of IP10. The unit features power dissipation of 14 Watts and supports flexible, rigid, and AWG 6 conductor sizes.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The NFD02.2-480-030 is a passive three-phase mains filter manufactured by Bosch Rexroth Indramat as part of the NFD Mains Filters series. It is installed ahead of servo drives, inverters, or power-supply modules to suppress radio-frequency noise, protect upstream equipment, and improve conducted electromagnetic compatibility on industrial automation lines. By inserting impedance across each line conductor, the filter reduces differential and common-mode disturbances that might otherwise propagate onto the plant mains. This helps limit interference between switching equipment and other devices connected to the same supply network.
Electrically, the filter is rated for AC 480 V +10% on a three-phase supply, which aligns with common North American motor distribution systems. Under continuous operation, it carries a rated mains current of 30 A, with internal inductive and capacitive elements matched to that load. Steady-state power dissipation is only 14 W, which helps keep thermal rise low and keeps cabinet airflow requirements modest. The housing has an IP10 rating, so the unit is finger-safe but still intended for installation inside an enclosure. Insulation integrity toward grounded conductors is verified at 2800 VDC for two seconds between line or neutral and protective earth. Because it is a passive filter, attenuation is provided without active control electronics or a separate power source.
Cable terminations accept rigid copper conductors up to 16 mm², while flexible wiring is supported at 10 mm² and matches AWG 6 strand size; the protective-earth connection must be at least 10 mm². During cyclic demand, the device tolerates an overload of 1.5 × IN for 1 min/h, allowing brief current surges without compromising attenuation performance. Dielectric spacing across phase paths is confirmed by a line-to-line withstand of 2125 VDC for two seconds. The filter weighs only 1.8 kg, which reduces mechanical load on the mounting panel and makes placement easier in compact enclosures.
Frequently Asked Questions about NFD02.2-480-030:
Q: What is the maximum mains voltage rating for the NFD02.2-480-030 filter?
A: The NFD02.2-480-030 mains filter supports a mains voltage of AC 480 V with an allowable fluctuation of up to +10%.
Q: How many phases does the NFD02.2-480-030 support?
A: This model is designed for three-phase applications, supporting a phase count of 3.
Q: What is the rated mains current for the NFD02.2-480-030?
A: The rated mains current for this filter is 30 A, allowing it to handle substantial electrical loads.
Q: What rigid conductor size should be used with the NFD02.2-480-030?
A: A conductor size of AWG 6 or 16 mm² is recommended for rigid wiring connections on this filter.
Q: What level of environmental protection does the NFD02.2-480-030 provide?
A: Its protection rating is IP10, indicating limited protection against solid objects greater than 50 mm and no protection against water.