NFD01.1-440-110 Bosch Rexroth Indramat
MPN: R911263208
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
The Bosch Rexroth Indramat NFD01.1-440-110 is part of the NFD Mains Filters series and is designed for use with a nominal voltage of 440 V and a rated current of 110 A. This three-phase mains filter features an IP10 protection rating and can withstand a ground test voltage of 2800 VDC and a line test voltage of 2125 VDC. It supports an overload capability of 1.5 times the rated current for up to 1 minute per hour.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The NFD01.1-440-110 is a passive three-phase mains filter manufactured by Bosch Rexroth Indramat within the NFD Mains Filters series. Installed ahead of drive controllers, it attenuates conducted electromagnetic noise and improves the power quality delivered to automation equipment. By adding inductance and capacitance between line and earth, the unit reduces high-frequency interference that could otherwise reach upstream feeders or nearby control electronics. This helps stabilize the incoming supply path for sensitive drive and control hardware in industrial cabinets.
At an ambient reference of 45 °C, the filter carries a continuous load of 110 A. Its nominal line voltage rating is 440 V, matching common industrial distribution levels and allowing connection directly to the incoming feeder without a step-down transformer. Designed for networks that supply three energized conductors, the phase count is 3, so the internal inductors and capacitors are arranged symmetrically across all phases. Short-term overload performance supports up to 1.5 × IN for no longer than 1 min/h, giving headroom for temporary current peaks during dynamic machine operation. The 45 °C current rating marks the thermal limit, so higher ambient temperatures require derating to prevent excessive capacitor heating or magnetic core saturation. This operating profile makes the filter suitable for drive systems that experience changing load conditions during normal use.
Dielectric integrity is verified by a ground isolation test of 2800 VDC between the filter chassis and each phase, while the inter-phase line test is performed at 2125 VDC. For a low-impedance protective earth path, the minimum PE conductor cross-section is 10 mm², sized to carry prospective fault currents without excessive temperature rise. The enclosure carries an IP10 rating, blocking accidental contact with live parts yet requiring placement inside a sealed cabinet for environmental protection. The filter should be mounted where cabinet wiring, grounding, and spacing can follow these electrical limits. Proper enclosure placement also helps keep dust, moisture, and incidental contact away from energized sections during operation.
Frequently Asked Questions about NFD01.1-440-110:
Q: What is the nominal voltage supported by the NFD01.1-440-110 mains filter?
A: The NFD01.1-440-110 mains filter operates at a nominal voltage of 440 V.
Q: What is the rated current capacity of the NFD01.1-440-110?
A: This model is rated for a maximum current of 110 A.
Q: How many phases does the NFD01.1-440-110 mains filter support?
A: The NFD01.1-440-110 mains filter has three phases.
Q: What is the protection rating of the NFD01.1-440-110 mains filter?
A: The protection rating for this unit is IP10.
Q: What overload capability does the NFD01.1-440-110 provide?
A: This filter can handle overloads up to 1.5 times the rated current for one minute per hour.