The Beckhoff KL3208 is part of the KL Analog Input Modules series and features 8 inputs for PT1000 sensors, supporting resistor ranges up to 655 kiloohms. This module offers a measuring error of plus or minus 0.25 degrees Celsius from -20°C to +60°C and a resolution of 0.01°C per digit. It is DIN rail mountable with IP20 protection and uses 2-wire wiring with 16 terminal points.

Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

The KL3208 is an analog input terminal manufactured by Beckhoff for the KL Analog Input Modules series. Installed beside a Bus Coupler on a DIN rail, it samples resistance temperature detectors and transfers the resulting digital values to the PLC process image. Its direct electrical interface for platinum sensors supports distributed temperature monitoring on packaging lines, food-processing heaters, and HVAC zones without separate signal conditioners. The modular housing allows the terminal to be installed with other Beckhoff input and output terminals in a compact control assembly.

Each channel is configured for a PT1000 reference element, and the terminal supports 8 inputs with a common ground. The input stage measures sensor resistances up to 650 kΩ, accommodating long lead lengths and compatible high-resistance probes without causing overrange faults. Conversion accuracy is maintained from -20 °C to +60 °C, with a maximum measuring deviation of ±0.25 °C. Installation uses a clip for a 35 mm DIN rail, and 16 push-in terminal points accept two-wire connections for the resistance sensors. In the controller, the input process image occupies eight status bytes and eight data words. The complementary output process image provides eight control bytes and eight data words for supported control functions.

The enclosure has an ingress protection rating of IP20, so the terminal must be installed inside a suitable control cabinet. The measuring circuitry recognizes compatible platinum or nickel elements across a temperature span of -50 °C to +150 °C. Its resolution is 0.01 °C per digit, allowing the controller to detect small temperature changes during operation. Three internal resistance ranges of 6 kΩ, 65 kΩ, and 655 kΩ are selected automatically to keep the converter within an appropriate measuring range. The terminal can be stored at temperatures from -40 °C to +85 °C when it is not operating. These storage limits accommodate unconditioned warehouse environments while the cabinet requirement protects the terminal during installed operation.

Default Sensor
PT1000
Input Process Image
8 Status Bytes (Opt.); 8 Data Words
Inputs
8
Max Sensor Resistance
650 kΩ
Measuring Error (-20°c To +60°c)
±0.25°C
Mounting
35 mm DIN Rail
Output Process Image
8 Control Bytes (Opt.); 8 Data Words (Opt.)
Protection Class
IP20
Pt/ni Temp Range
-50°C to +150°C
Resistor Ranges
6 kΩ; 65 kΩ; 655 kΩ
Resolution
0.01°C Per Digit
Storage Temperature
-40°C to +85°C
Terminal Points
16
Wiring
2-Wire

Frequently Asked Questions about KL3208:

Q: What type of sensor does the Beckhoff KL3208 module support by default?

A: The KL3208 module is equipped to work with PT1000 sensors by default.

Q: How many input channels does the KL3208 support?

A: This module can read up to 8 individual inputs simultaneously.

Q: What is the measuring accuracy of the KL3208 analog input module?

A: The KL3208 has a measuring error of ±0.25°C within the temperature range of -20°C to +60°C.

Q: What resolution does the KL3208 provide for temperature measuring?

A: Temperature values are displayed with a resolution of 0.01°C per digit on this module.

Q: How is the KL3208 module installed in an enclosure?

A: The KL3208 mounts to a 35 mm DIN rail for easy installation in control cabinets.


Internal Product Review

  • ‘‘The KL3208 is a Beckhoff analog input module designed for 8 inputs and PT1000 sensing. Measurement performance is impressive, with ±0.25°C accuracy from -20°C to +60°C and 0.01°C resolution per digit. DIN rail mounting and IP20 protection make the unit a strong fit for controlled cabinet installations.’’