The KL3202-0014 analog input module supports 2- or 3-wire connection methods, features a measurement error of less than ±1°C, offers a typical measuring current of 0.5 mA, and has an EMC immunity that conforms to EN 61000-6-2 standards. Part of the KL Analog Input Series by Beckhoff, it accommodates Pt and Ni sensors with a resolution of 0.1°C per digit.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
This resourceful product KL3202-0014 from Beckhoff is a Bus Terminal designed for temperature measurement in industrial automation setups. Beckhoff is a high-grade company that designs high-performance electrical and mechanical components needed for large- and small-scale requirements.
This KL3202-0014 terminal bus has two analog input channels and supports a wide range of resistance temperature detectors (RTDs) like Pt100, Pt200, Pt500, Pt1000, as well as nickel-based sensors like Ni100, Ni120, and Ni1000. Also, it can be used for resistance measurement such as for potentiometers within a range of 10 ohms to 1.2/5 kohms. One of the main advantages of this KL3202-0014 terminal bus is its flexibility in handling both 2-wire and 3-wire connections with 3-wire being the default for more accurate measurements. This device can measure temperatures in a broad range from -200°C to +850°C with Pt sensors, and -60°C to +250°C with Ni sensors for those applications requiring precise temperature monitoring. It converts analog signals to digital format with a 16-bit resolution by ensuring precise temperature readings with a measurement uncertainty of less than ±1°C. It also offers a high level of electrical isolation at 500 V between the K-bus and signal voltage by enhancing operational safety. It works with a typical current consumption of 60 mA from the K-bus and no need for an additional power.
The KL3202-0014 terminal bus has a compact design which actually measures 12 mm in width which helps in allowing for space-saving installation on a standard 35 mm DIN rail. It is built to function in harsh environments as in temperatures from -25°C to +60°C and is vibration and holds a shock resistant property conforming to set standards. The terminal is also EMC compliant and carries multiple certifications including CE, UL, ATEX, and IECEx by mainly ensuring its use in a variety of industrial settings.
Frequently Asked Questions about KL3202-0014:
Q: What types of temperature sensors are compatible with the KL3202-0014?
A: The KL3202-0014 supports various RTDs, including Pt100, Pt200, Pt500, Pt1000, as well as Ni100, Ni120, Ni1000 sensors by offering versatility in temperature measurement applications.
Q: How many input channels does the KL3202-0014 have?
A: The KL3202-0014 Bus Terminal features two analog input channels enabling temperature measurements from two sensors simultaneously.
Q: What is the typical conversion time of the KL3202-0014?
A: The KL3202-0014 has a typical conversion time of approximately 250 ms by ensuring responsive temperature measurement for real-time applications.
Q: Can the KL3202-0014 be used with a 2-wire connection?
A: Yes, the KL3202-0014 supports both 2-wire and 3-wire configurations although 3-wire is the default for enhanced accuracy.
Q: What is the level of measurement accuracy for the KL3202-0014?
A: The KL3202-0014 offers a measurement accuracy with an uncertainty of less than ±1°C by delivering highly reliable temperature readings.