KL3112 Beckhoff
Wake Industrial LLC is not an authorized distributor of this product.
MPN: KL3112-0000
The Beckhoff KL3112 module, part of the KL Analog Input Modules series, features 2 signal current inputs ranging from 0 to 20 mA. It offers a 15-bit resolution configurable to 16-bit and a conversion time of 140 ms adjustable to 2 ms. Operating temperatures span 0–55°C, with a typical K-bus current consumption of 60 mA.
Internal Product Review
The Beckhoff KL3112 Bus Terminal offers two differential inputs and 35 V surge protection for industrial reliability. Its 15-bit default resolution, expandable to 16 bits, ensures accurate current measurement. The unit features 500 V electrical isolation and real-time LED diagnostics. It is ideal for compact, precise automation setups.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The KL3112 Bus Terminal is a compact high precision analog input device for automation systems. It measures currents between 0 and 20 mA with electrical isolation from the automation controller. It combines two input channels in one housing and provides differential signal processing. It supports seamless data exchange via the K bus system.
The Beckhoff KL3112 bus terminal detects open leads or overloads and relays status updates through the system. The terminal supports two differential inputs each handling current signals from 0 to 20 mA. Its internal shunt resistance is typically 50 Ω while the load condition is 60 Ω plus diode voltage. The model can withstand a maximum common mode voltage of 35 V and offers surge resistance up to 35 V DC. The resolution is adjustable set by default at 15 bits but configurable up to 16 bits for greater accuracy. Conversion time of the terminal is 140 ms but can be tuned down to 2 ms if needed. Electrical isolation between the K bus system communication and the analog input channels is rated at 500 V RMS. This provides robust protection against ground loops and external interference. The terminal is designed for reliable operation in industrial environments with significant electromagnetic disturbance.
The KL3112 bus terminal material is polycarbonate that contributes to durability while keeping the weight low. It is built in a compact housing with integrated signal LEDs for real time diagnostics. The bus terminal incorporates a configurable 50 Hz low pass filter to effectively suppress mains related noise. It maintains a maximum measurement error of ± 0.3 % that ensures high accuracy signal acquisition. Wake Industrial offers this bus terminal with a replacement warranty.