The KL1302 is a compact analog input module featuring two digital inputs and a 2-wire connection technique. Designed by Beckhoff as part of their KL Analog Input Modules series, it operates with an input voltage of 24 V DC (-15%/+20%). The module measures 12 mm x 100 mm x 68 mm and is CE, UL, and ATEX certified.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The KL1302 Beckhoff bus terminal comprises digital inputs that comply with Type 2 input specifications. This terminal has two channels to support the operation. The product houses light emitting diodes to display the channel-related signal states. This device features a 24 VDC voltage. The unit’s input filter has a speed of 3 ms. It comprises a polycarbonate housing with LEDs. This terminal permits operation in explosive atmospheres.
The product depicts a variable installation position, although the horizontal position is preferred and a protection class of IP 20. This device’s shock resistance conforms to EN 60068-2-27 specifications. The unit’s DIN mounting rail has a locking mechanism and a 35 mm thickness. It offers three wiring options. This terminal’s original state must not be modified. The product-related control cabinet must comprise an IP 54 protection degree or higher. This device supports operation in explosion-prone areas. The unit-associated operating voltage cannot exceed 40% of the rated value. Its front part can be opened only in non-explosive areas after the supply voltage has been switched off.
This terminal is compatible with Type 2 sensors. The product is UL listed, Ex marked, and CE certified. This device and its fieldbus are connected with a bus coupler specified for this connection. The unit housing supports a DIN rail mounting action. It helps in the binary signals acquisition process. This bus terminal operation in confined spaces with no effort is possible because of its compact construction and its lightweight profile helps in easy relocation from one place to another.
Frequently Asked Questions about KL1302:
Q: What is the voltage rating of the KL1302 terminal?
A: The voltage rating of the KL1302 terminal is 24 VDC with -15%/20% tolerance.
Q: What is the input current of the inputs of the KL1302 terminal?
A: The input current of the inputs of the KL1302 terminal is 6 mA.
Q: How many sensors can be connected to the KL1302 terminal?
A: Two sensors can be connected to the KL1302 terminal.
Q: What is the connection cross-section of the KL1302 terminal with ferrule wiring?
A: The connection cross-section of the KL1302 terminal with ferrule wiring is 0.4 mm² to 1.5 mm² or AWG 26 to 16.
Q: Does the KL1302 terminal support side-by-side mounting?
A: Yes, the KL1302 terminal support side-by-side mounting using a key connection and a double slot.