4.94 based on 220 reviews

🙶 Easy to navigate website and quick responses from support. Additionally, pretty fast shipping. Our mainte... 🙷

EP1816-3008 Beckhoff

In-Stock, Ships 3-5 Days
No Hidden Fees Rush or Credit Card
No Tariffs On US Orders

Internal Product Review

The EP1816-3008 is a Beckhoff EP digital input module with 16 digital inputs and Type 3 input characteristics per EN 61131-2. Integrated condition monitoring adds strong value through two 3-axis accelerometers in a 90° offset layout and 10-bit acceleration resolution. A 500 µs minimum cycle time makes this module a very capable choice for high-response EtherCAT installations.

Sell Part
Have a part to sell?
Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

The EP1816-3008 is a distributed I/O device produced by Beckhoff within the EP Digital Input Modules series. It mounts directly on the machine frame and connects to an EtherCAT network segment, where it provides 16 type 3 digital inputs for 24 V control circuits while also hosting two integrated 3-axis accelerometers oriented 90° to each other for vibration analysis. By combining signal acquisition and condition monitoring in one housing, the module reduces cabinet wiring and provides time-synchronized data to the main controller over the EtherCAT network.

The input stage is designed for a nominal bus voltage of 24 V DC, and each channel draws only 3 mA, keeping sensor loading low. Input transitions are conditioned by a filter of 10 µs, allowing fast-switching sensors to be captured without contact bounce appearing in the PLC process image. The minimum EtherCAT cycle time is 500 µs; at this rate, the device can refresh its process image during every network cycle. Internal sampling supports a transfer rate of up to 2.5 kHz, helping prevent input edges from being lost between frames. The digital front end follows EN 61131-2 type 3 requirements, which allow sensors with either PNP or push-pull outputs to be connected without additional adapters.

Galvanic isolation between the EtherCAT circuitry and the field side is rated at 500 V, protecting upstream hardware from wiring faults. Field wiring may extend up to 30 m per channel, enabling the module to remain close to actuators while the controller cabinet is located remotely. Up to 0.5 A of sensor power is available through the 25-pin D-sub signal connector, and all network traffic passes through two M8 A-coded sockets arranged for a daisy-chain topology. Acceleration data is delivered at 10-bit resolution. Undervoltage detection below 18 V triggers a diagnostic flag so the controller can react before the inputs misinterpret a low supply voltage.

Acceleration Resolution
10-bit
Accelerometer Layout
Two 3-axis, 90° offset
Digital Input Count
16
Digital Input Type
Type 3 per EN 61131-2
Ethercat Connection
2 x M8 socket, 4-pin, A-coded, shielded
Ethercat Isolation
500 V
Input Current
3 mA
Input Filter
10 µs
Max Cable Length
30 m
Max Transfer Rate
2.5 kHz
Minimum Cycle Time
500 µs
Nominal Input Voltage
24 VDC
Sensor Power Max
0.5 A
Signal Connection
D-sub socket, 25-pin, UNC4-40 thread
Undervoltage Detection
<18 V
Us Nominal Voltage
24 VDC

Frequently Asked Questions about EP1816-3008:

Q: How many digital inputs does the EP1816-3008 module offer?

A: The EP1816-3008 module features 16 digital inputs conforming to Type 3 per EN 61131-2 standards.

Q: What is the acceleration resolution of the EP1816-3008?

A: A 10-bit acceleration resolution is provided by the EP1816-3008 for precise measurement tasks.

Q: What is the maximum cable length supported by the EP1816-3008?

A: The EP1816-3008 supports a maximum cable length of 30 meters for signal connections.

Q: What nominal input voltage does the EP1816-3008 require?

A: A nominal input voltage of 24 VDC is required for proper operation of this module.

Q: What type of EtherCAT connection is used on the EP1816-3008?

A: The EtherCAT connection on the EP1816-3008 utilizes two M8 4-pin shielded A-coded sockets.

Motion Industries logo
3M logo
IBM logo
Gexpro Logo
Caterpillar logo
NASA logo
Ford logo
Vallen logo