3DI486.6/T B & R Automation
Wake Industrial LLC is not an authorized distributor of this product.
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
Current response time:
6 Minutes
31 Seconds
The B & R Automation 3DI486.6/T is part of the System 2005 Controllers series and is equipped with 32 inputs, divided into two groups of 16, with 32 input status LEDs. It operates at a nominal input voltage of 24 VDC, supports input resistances of 6 kΩ, and features isolation between PLC and input groups with shared isolation within each group. Maximum input voltage is 30 VDC, and the module consumes up to 1.2 W of power.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The 3DI486.6/T digital input card is produced by B & R Automation as part of the System 2005 Controllers series. It plugs into a controller rack and gathers discrete field signals from sensors, limit switches, and operator devices used in automated machinery. By translating DC levels into internal logic, the card enables the central processor to monitor equipment states, trigger interlocks, and coordinate sequencing tasks required for reliable industrial operation.
An input is recognized as on once the dock-on level exceeds 18 VDC, yet the nominal control level remains 24 VDC so the module interfaces with standard plant supplies. Each channel presents an input resistance of 6 kΩ, which limits current draw to about 4 mA and reduces electrical load on upstream sensors. The card is arranged as two groups of 16 inputs, and each channel has a status indicator so a bank of 32 LEDs can be checked at a glance. A galvanic barrier separates each group from the PLC, but inputs within a group share a common return. Under worst-case conditions, the logic change reaches the controller within 1 ms. Total power demand stays low at 1.2 W, which helps with thermal management in dense cabinets.
The accepted input range extends up to 30 VDC, helping prevent misreads when supply rails drift, and typical propagation of 0.5 ms supports rapid response to changing field states. Surge suppression is integrated, and the front end tolerates transients of 500 V / 50 µs / 100 ms without damage, which is useful in panels where inductive loads switch frequently. Field wiring terminates on 2 x 18-pin removable blocks, which keeps conductors organized and simplifies service access. The PLC, group, and channel isolation scheme keeps ground noise localized and helps maintain stable logic levels during simultaneous switching events.
Frequently Asked Questions about 3DI486.6/T:
Q: What is the nominal input voltage for the 3DI486.6/T controller?
A: The B & R Automation 3DI486.6/T has a nominal input voltage of 24 VDC.
Q: How many input channels does the 3DI486.6/T controller provide?
A: This model supports a total of 32 inputs grouped into 2 x 16 input groups.
Q: How are input statuses indicated on the 3DI486.6/T controller?
A: The input status for all channels is displayed via 32 individual LEDs.
Q: What type of terminal blocks are used for wiring on the 3DI486.6/T?
A: This module uses two 18-pin terminal blocks for wiring connections.
Q: What is the isolation topology of the 3DI486.6/T controller?
A: The 3DI486.6/T features group-level isolation between the PLC and input groups, with inputs in the same group sharing isolation.